The CRA-310 transmitter is applicable to the measurement of differential pressure of gases, vapours and liquids. The active element is a piezoresistant silicon sensor separated from the medium by separating diaphragm and a specially selected type of manometric fluid. The electronics is placed in a casing with a degree of protection IP 54.
The electrical connection is a DIN 43650 connector. Potentiometers can be used to shift the zero position and the range by up to 10%, without altering the settings. The transmitter is not heavy, so it can be installed directly onto impulse lines. For fitting in any desired position on a Ø25 pipe the mounting bracket is recommended. The version with C type process connection can be fitted directly to a 3- or 5-valve manifold. The factory-mounted transmitters with VM type valve manifold are recommended. A transmitter without a valve manifold can be fitted in any position on a 2" pipe or on a wall using the C-2" mounting bracket. When the special process connections are required for the measurement of levels and pressures (e.g. at food and chemical industries), the transmitter is provided with a diaphragm seal.
Measurement range |
0...2 kPa up to 0...1600 kPa
|
Output type |
4...20 mA, 2-wire
0...10V, 3-wire
0...20 mA, 3-wire
|
Process connection |
M20x1,5
|
Electrical connection |
DIN 43650 connector
|
Diaphragm |
stainless steel 316L
Hastelloy C 276
|
Power supply |
10…39V DC
13…39V DC
|
Accuracy |
±0,25%
±0,4%
|
Operating temperature |
-25…+80°C
|
Medium temperature |
-25...+120°C
|
Protection class |
IP 54
|
Case material |
stainless steel
|
Data sheet EN |