Description
Isolators SGS-12 series create galvanic isolation between input and output circuits. Isolator doesn’t need any power supply. 0/4-20 mA current output signal can also be processed into voltage 0/2-10V signal with standard 500Ω load resistance. Then for class 0,5% it is advised to use voltage input R ≥ 100 kΩ. Quality of isolation depends on breakdown voltage and also capacity between separated circuits.
Specification
Number of inputs |
1
2
|
Input type |
current (mA)
|
Input range |
0/4...20 mA
|
Number of outputs |
0
1
2
|
Output type |
0...20 mA
4...20 mA
|
Galvanic isolation |
2kV, 100pF
between input and output circuit
|
Load resistance |
0...1000Ω
|
Power supply |
current loop
21...28V DC
|
Protection class |
IP 20
|
Operating temperature |
-20...+60°C
|
Mounting |
DIN rail
|
Case dimensions |
12,5 x 99 x 114,5 mm
|
Files
Data sheet | |
Brochure EN | |
Declaration of conformity |