The SWE-94-U meter is equipped with one universal input: 0/4-20 mA, 0-10V, 0-150 mV, RTD (Pt 100/500/1000) or thermocouple (K, S, J, T, N, R, B, E). Temperature of cold ends is compensated automatically. RTD and TC inputs are fully linearised. It is allowed to use only one input at the same time. SWE-94-U enables user to select a characteristic conversion of several kinds: linear, square, square root, user defined. The device is equipped with RS-485 / Modbus RTU communication interface. Over more communication interface RS-485 enables data transmission in any monitoring system equipped with Modbus RTU protocol. The meter can be ordered in 3 power supply versions. The meter can be configured with IR remote controller or free S-Config software via the RS-485 communication port.
Number of inputs |
1
|
Input type |
universal
|
Input range |
0/4...20 mA
0/1...5V, 0/2...10V
0...60 mV, 0...75 mV, 0...100 mV, 0...150 mV
Pt100, Pt500, Pt1000: -100...+600°C
TC K: -200...+1370°C, S: -50...+1768°C, J: -210...+1200°C, T: -200...+400°C, N: -200...+1300°C, R: -50...+1768°C, B: +250...+1820°C, E: -200...+1000°C
0...300Ω, 0...3kΩ
|
Output type |
no output
|
Power supply |
110V AC
230V AC
10…30V DC
|
Display |
LED, 4 x 20 mm, red
|
Communication Interface |
RS-485 / Modbus RTU
|
Transmission parameters |
1200...115200 bit/s, 8N1 / 8N2
|
Operating temperature |
0...+50°C
-20…+50°C
|
Protection class |
IP 20 (case and connection clips)
IP 40 (front)
optional integrated frame for panel cut-out sealing
|
Case material |
NORYL UL94 V0
|
Mounting |
panel
|
Case dimensions |
96 x 48 x 72 mm
|
Data sheet | |
Manual EN | |
Declaration of conformity |