Loading

SUR-W410

Code: SUR-W410
  • large-size universal meter
  • 100 mm LED display, red
  • universal input: 0/4-20 mA, 0-10V, 0-150 mV, RTD or TC
  • binary outputs REL / OC
  • analogue output: active or passive, power supply output: 24V DC
  • RS-485 / Modbus RTU
  • signal peak value detection
  • free configuration S-Config software
Description

The SUR-W410 meter is equipped with one universal input, type: 0/4-20 mA, 0-10V, 0-150 mV, Pt 100/500/1000 or TC (K, S, J, T, N, R, B, E). During the measurement process only one kind of input is available. Due to wide range of characteristic curves (linear, square root, quadratic, user-defined and volume characteristic for cylindrical tanks) the meters may be used in various process control systems. As a main advantage, this device is equipped with a large, 100 mm high, LED display with brightness adjustable in 8 steps. The device has 4 buttons being used for main presets programming. To get high protection level, the keyboard is mounted under transparent cover. To allow user to change presets without opening the cover, an IR sensor is mounted. The 24V DC / 100 mA output is designed to supply measuring transducers, and the RS-485 port enables data transmission in production process monitoring systems. The REL / OC control outputs can adjust the level of measured signal and are controlled according to one or two threshold values. Moreover, the meter can be equipped with analogue outputs, according to the customer selection: active current output, passive isolated current output or active voltage output. The meter may be configured with no need to open the case, by using the remote controller or with free S-Config software via the RS-485 communication port.

Specification
Number of inputs
1
Input type
universal
Input range
0/4...20 mA
0...60 mV, 0...75 mV, 0...100 mV, 0...150 mV
0/1...5V, 0/2...10V
0...300Ω, 0...3kΩ
Pt100, Pt500, Pt1000: -100...+600°C
TC K: -200...+1370°C, S: -50...+1768°C, J: -210...+1200°C, T: -200...+400°C, N: -200...+1300°C, R: -50...+1768°C, B: +250...+1820°C, E: -200...+1000°C
Output type
depends on configuration:
relay I=1A, U=30V DC/250V AC (cosø=1)
Open Collector: I=30 mA, U=30V DC, P=100 mW
0/4...20 mA: active current, operating range 0...24 mA max., load resistance 700 Ω max., resolution 13 bit
4...20 mA: passive current, isolated, operating range 2,8...24 mA max., load resistance 600 Ω@24VDC, resolution 13 bit
0/1...5V, 0/2...10V: active voltage, operating range 0...11V max., load resistance min. 2000 Ω, resolution 13 bit
Power supply
16...35V AC, 19...50V DC
85..260V AC/DC
Display
LED, 4 x 100 mm, red
Communication Interface
RS-485 / Modbus RTU
Transmission parameters
1200...115200 bit/s, 8N1 / 8N2
Operating temperature
0...+50°C
-20…+50°C
Protection class
IP 30
Case material
methyl polimethacrylate (PMMA)
aluminium
Mounting
wall
Case dimensions
578 x 208 x 102 mm